Fire Extinguisher Placement Calculator (NFPA 10 (2022) Tables 6.2.1.1 and 6.3.1.1)
Number of Class A extinguishers by floor area and travel distance, and the Class B travel distance for a rating. The calculation runs in your browser. A free account is needed after 3 calculations and to download results. Saving a project stores the inputs with your account.
Guide: Fire Extinguisher Placement
- Load the sample to see typical inputs, then replace every value with your project data.
- Check the units shown next to each input.
- Calculate, then read the step-by-step table and any warnings. Verify the result before using it in a design.
Code basis and design decisions
- Class A (NFPA 10 Table 6.2.1.1): minimum single extinguisher 2-A light hazard, 2-A ordinary, 4-A extra; maximum floor area per unit of A 3,000, 1,500 and 1,000 ft2; maximum floor area per extinguisher 11,250 ft2; maximum travel distance 75 ft.
- Count = ceil(floor area / min(rating × area per unit of A, 11,250)). With the building length and width, the app also counts a square grid whose corners are 75 ft from each extinguisher (cell 106 ft) and takes the larger number.
- Class B (NFPA 10 Table 6.3.1.1, liquids 1/4 in. deep or less): light 5-B within 30 ft or 10-B within 50 ft; ordinary 10-B / 30 ft or 20-B / 50 ft; extra 40-B / 30 ft or 80-B / 50 ft.
Notes & limits
- Travel distance is measured along the actual walking path around walls, partitions and racks. The grid count is an open-floor estimate: lay the extinguishers out on the plan and check every point is within 75 ft.
- Each floor is counted separately. Extinguishers for Class B of appreciable depth, Class C, D and K hazards follow other NFPA 10 sections.
- The authority having jurisdiction may require more extinguishers.