Fire Extinguisher Placement Calculator (NFPA 10 (2022) Tables 6.2.1.1 and 6.3.1.1)

Number of Class A extinguishers by floor area and travel distance, and the Class B travel distance for a rating. The calculation runs in your browser. A free account is needed after 3 calculations and to download results. Saving a project stores the inputs with your account.

Guide: Fire Extinguisher Placement
  1. Load the sample to see typical inputs, then replace every value with your project data.
  2. Check the units shown next to each input.
  3. Calculate, then read the step-by-step table and any warnings. Verify the result before using it in a design.
Code basis and design decisions
  • Class A (NFPA 10 Table 6.2.1.1): minimum single extinguisher 2-A light hazard, 2-A ordinary, 4-A extra; maximum floor area per unit of A 3,000, 1,500 and 1,000 ft2; maximum floor area per extinguisher 11,250 ft2; maximum travel distance 75 ft.
  • Count = ceil(floor area / min(rating × area per unit of A, 11,250)). With the building length and width, the app also counts a square grid whose corners are 75 ft from each extinguisher (cell 106 ft) and takes the larger number.
  • Class B (NFPA 10 Table 6.3.1.1, liquids 1/4 in. deep or less): light 5-B within 30 ft or 10-B within 50 ft; ordinary 10-B / 30 ft or 20-B / 50 ft; extra 40-B / 30 ft or 80-B / 50 ft.

Inputs

Notes & limits