Hydrant Flow Test & Supply Curve Calculator (NFPA 291, Q = 29.83 c d² √p)
Turn hydrant flow test readings into flow, available flow at a target residual pressure and a supply curve. The calculation runs in your browser. A free account is needed after 3 calculations and to download results. Saving a project stores the inputs with your account.
Guide: Hydrant Flow Test & Supply Curve
- Load the sample to see typical inputs, then replace every value with your project data.
- Check the units shown next to each input.
- Calculate, then read the step-by-step table and any warnings. Verify the result before using it in a design.
Code basis and design decisions
- Outlet flow: Q = 29.83 × c × d2 × √p (NFPA 291), d = actual outlet inside diameter in inches, p = pitot pressure in psi, c = 0.90 smooth well-rounded outlet, 0.80 square and sharp, 0.70 square projecting into the barrel.
- Available flow at a residual pressure: QR = QF × ((S − Rt)/(S − R))0.54 (NFPA 291), with 20 psi the usual target.
- Supply curve plotted on N1.85 paper, where the test line is straight. The optional demand point (flow and pressure at the connection) is checked against the curve.
- NFPA 291 recommends a test pressure drop of at least 10 psi; the app warns when it is smaller.
Notes & limits
- The 0.54 exponent assumes Hazen-Williams behaviour of the supply; it is the NFPA 291 method, not a network model.
- Use the actual outlet inside diameter, measured, not the nominal size, and the pitot reading at the centre of a full stream.
- Demand pressure must be at the same point and elevation as the test residual gauge; adjust for elevation and friction to the connection yourself.