Hydrant Flow Test & Supply Curve Calculator (NFPA 291, Q = 29.83 c d² √p)

Turn hydrant flow test readings into flow, available flow at a target residual pressure and a supply curve. The calculation runs in your browser. A free account is needed after 3 calculations and to download results. Saving a project stores the inputs with your account.

Guide: Hydrant Flow Test & Supply Curve
  1. Load the sample to see typical inputs, then replace every value with your project data.
  2. Check the units shown next to each input.
  3. Calculate, then read the step-by-step table and any warnings. Verify the result before using it in a design.
Code basis and design decisions
  • Outlet flow: Q = 29.83 × c × d2 × √p (NFPA 291), d = actual outlet inside diameter in inches, p = pitot pressure in psi, c = 0.90 smooth well-rounded outlet, 0.80 square and sharp, 0.70 square projecting into the barrel.
  • Available flow at a residual pressure: QR = QF × ((S − Rt)/(S − R))0.54 (NFPA 291), with 20 psi the usual target.
  • Supply curve plotted on N1.85 paper, where the test line is straight. The optional demand point (flow and pressure at the connection) is checked against the curve.
  • NFPA 291 recommends a test pressure drop of at least 10 psi; the app warns when it is smaller.