Occupant Load Calculator IBC Table 1004.5, exits and egress width

List the spaces on a story with their function and floor area. Get the occupant load, the minimum number of exits and the egress capacity width. Updates as you type. The calculation runs in your browser. A free account is needed after 3 calculations and to download results. Saving a project stores the inputs with your account.

Guide: Occupant Load
  1. Load the sample to see typical inputs, then replace every value with your project data.
  2. Check the units shown next to each input.
  3. Results and the drawing update as you type. Read the step-by-step table and any warnings.
Code basis and design decisions
  • Load factors: FBC 2023 Building (8th edition) Table 1004.5: floor area in ft2 per occupant, gross or net as listed. Each space is rounded up to a whole occupant (editable engineering default; the code gives no rounding rule).
  • Fixed seating: counted by seats (1004.6). Bowling: 5 persons per lane including 15 ft of runway. Concentrated business use: 50 gross (1004.8).
  • Exits: Table 1006.3.2 per story: 2 for 1–500, 3 for 501–1,000, 4 above 1,000. Width: 1005.3.1 stairs 0.3 in and 1005.3.2 other components 0.2 in per occupant (0.2 / 0.15 with sprinklers and emergency voice/alarm, not H or I-2).
  • One exit from a space: Table 1006.2.1 maximum occupant load (A, B, E, F, M, U, R-2, R-3 49; S 29; R-4 20; R-1, I-1 to I-4, H-4, H-5 10; H-1 to H-3 3), also subject to the common path of egress travel limits.