Engineering aid only. Professional verification required. The method notes and tags on this page are the references this app cites.
By running a calculation you agree to the Terms of Use and Privacy Policy. Results are preliminary and must be verified by a licensed professional.
No local parking code table is built in. Required parking varies by jurisdiction: every ratio below is the one you enter. Confirm the ratios, any shared-parking allowance, the accessible-space rules and the stall dimensions with the authority having jurisdiction.
Method, assumptions and limits (read before use)
Required spaces: for each land use you enter a quantity (for example square feet), a ratio and what the ratio is per: spaces = quantity × ratio / per (3.5 per 1000 sf is ratio 3.5, per 1000; “per” has no default). Mixed uses are added. Everything is rounded up to whole spaces (a value within 0.000000001 of a whole number counts as that number): rounding “per_use” (default) rounds each use then adds, “total” adds then rounds once.
Shared parking:shared_method “none” (default), “factor” (you enter the percent reduction, 0 to 60; over 30 is warned) or “profile”: the time-of-day method described for the ULI Shared Parking model (Urban Land Institute, ICSC and National Parking Association, Shared Parking, 3rd edition, 2020). For every use you enter the percent of its peak demand present in each period (2 to 48 periods); the periods are summed across uses and the largest total governs. The ULI base ratios and factor tables are not included: take your percentages from the book, a local study or ITE Parking Generation data. Seasonal, captive-market and mode-share adjustments are not computed (fold them into your percentages).
Accessible spaces (2010 ADA Standards, Table 208.2), for the total spaces provided in one parking facility (run each lot or structure separately): 1 to 25: 1; 26 to 50: 2; 51 to 75: 3; 76 to 100: 4; 101 to 150: 5; 151 to 200: 6; 201 to 300: 7; 301 to 400: 8; 401 to 500: 9; 501 to 1000: 2 percent of the total; 1001 and over: 20 plus 1 for each 100, or fraction thereof, over 1000. Fractions round up (104.2), so 501 spaces need 11. The accessible spaces are part of the total. Van spaces (208.2.4): for every six or fraction of six accessible spaces, one is a van space (ceil(accessible / 6)).
Special cases: ada_category “hospital_outpatient” (208.2.1): 10 percent, and “rehab_mobility_pt” (rehabilitation facilities specializing in conditions that affect mobility and outpatient physical therapy facilities, 208.2.2): 20 percent, of the patient and visitor spaces serving that use, rounded up (enter patient_visitor_spaces; if left out all spaces of the use are treated as patient and visitor spaces and this is warned). Per 208.2.1 and 208.2.2 the patient and visitor spaces are counted at 10 percent or 20 percent, and all other spaces in the facility are counted under Table 208.2 as one pool (the reading used here); confirm it with your building official. Doctors’ offices and clinics outside a hospital are “general”.
Spaces provided: if you enter spaces_provided the accessible and EV-ready counts use it and a count below the spaces required fails the gating check; otherwise the spaces required are used, with a warning (Table 208.2 is based on the spaces provided). EV-ready:ev_ready_pct × those spaces, rounded up; what counts as EV-ready, EV-capable or a charger is set by your jurisdiction.
Layout check (90, 60, 45 or 30 degrees; stall width w, stall length L along its axis, aisle width A): stall projection SP = L sinθ; stall width along the aisle w / sinθ; base (double-loaded) module M1 = 2 SP + A; single-loaded module M2 = SP + A, a conservative figure that the result shows next to the smaller printed value (for example 39.00 ft for a 9 ft × 18 ft stall at 60°, two-way aisle); stall length is measured along the stall’s own axis (a depth square to the aisle is L sinθ); interlock w cosθ / 2; the wall-to-wall stall envelope module 2 (L sinθ + w cosθ) + A is also given because rectangular stripe layouts measure it. The fit check against your available width uses M1. The published wall-to-interlock modules and wheel stops, overhang, curbs and columns are not modelled.
Checks: the limits you enter (minimum stall width, length, aisle width; available module width) and spaces provided against required are gating. The typical minimums are advisory (they warn and never change the verdict): typical stall width and length per the Iowa State University InTrans Design Manual, Chapter 8 (ULI / NPA); the typical aisle width for a 9 ft × 18 ft stall at the angle and aisle direction you choose, from the Iowa State University InTrans Design Manual, Chapter 8, Table 8B-1.02 (adapted from ULI / NPA, The Dimensions of Parking) (the result shows the one value used, with this citation); the 30° one-way aisle from the University of Arkansas campus standards. The source table allows the aisle to be 1 ft narrower where at least 30 percent of the stalls have curbs; that reduction is not applied, so the typical aisle values are the unreduced ones. They are not code requirements, local codes differ, and no typical value is cited for a 30° two-way aisle.
Defaults (each echoed in “defaults used” and warned): rounding “per_use”, shared_method “none”, aisle direction “two_way”, and the spaces required when spaces_provided is left out. No check, no verdict: when no gating check can run (for example only land uses are entered, or a layout with no minimum or available width of your own) the result is shown as not evaluated, never as a pass. Edition: 2010 ADA Standards for Accessible Design (36 CFR part 1191 appendices B and D); state and local accessibility codes can require more.
Inputs are strict: numeric values must be numbers (text is rejected); misspelled or unknown fields are rejected with a suggestion; a null is rejected (leave the field out); numbers in meta must be below 1e15; labels are at most 80 characters; at most 30 land uses and 48 profile periods. Results are engineering aids; a licensed engineer must review before sealing.
Out of scope: residential parking requirements (ADA 208.2.3), bus, truck and delivery-vehicle spaces, passenger loading zones, accessible route, signage and stall striping dimensions (ADA 208.3, 502; for reference a car space is 96 in wide, a van space 132 in wide with a 60 in access aisle or 96 in with a 96 in aisle), parking structures’ ramps and circulation, turning radii, drainage, lighting, bicycle parking, and metric units.