Code edition and design decisions (NEC 2023)
Code edition: NEC (NFPA 70) 2023, Chapter 9: Table 1 (53 % one conductor, 31 % two, 40 % over two), Note 4 (60 % for nipples 24 in. or less), Table 4 (raceway areas), Table 5 (insulated conductor areas), Table 8 (bare conductors, Note 8), Note 7 (rounding) and Annex C. Table values were compared across the 2017 NEC text and 2023-labelled reproductions. THW/THW-2/THHW at 14, 12, 10 and 8 AWG use 0.0139, 0.0181, 0.0243 and 0.0437 in2 (the 2017 text; RHH*/RHW*/RHW-2* have their own values). The EMT results are checked cell by cell (1360 cells, five insulation groups, the TW block for THW 14-8) against an NECA copy of Annex C Table C.1, which is the 2011 edition; THW 14-8 follow the 2017 text. All values are to be confirmed against the printed NFPA 70-2023 by a licensed reviewer.
- Required inputs, no defaults: raceway type, nipple answer, rounding rule and the conductor list. Only the trade size to check is optional (blank = just find the smallest size).
- Rounding rule (you choose): strict compares total conductor area with the Table 1 percent of the Table 4 area. note7 applies Note 7 to conductors that are all the same size and type (one group): a permitted count with a decimal of 0.8 or more is rounded up, which matches Annex C and can allow a fill slightly above the percent limit. Several lines of the same type and size (for example phases and neutral) are merged into one group first; different types or sizes are not. The fill percent is always shown and flagged on its own.
- Conductor count for Table 1 is the total number of conductors entered, including an equipment grounding or bonding conductor (Note 3). Enter it as its own line. A multiconductor cable counts as one conductor (Note 9): use type custom with its actual overall area. Assemblies of single insulated conductors without an overall covering are not a cable (Note 9): enter them as individual conductors, not as one custom area.
- Exact arithmetic: the fill percent is shown rounded up to 0.01 % and pass means the shown value is at or below the limit. Table 4 prints its percent columns rounded to 0.001 in2; this page takes the percent of the exact 100 % column.
- Areas: Table 5 approximate (worst-case, Note 10) areas for THHN/THWN/THWN-2, XHHW/XHHW-2, THW/THW-2/THHW, RHH/RHW/RHW-2 (with and without outer covering) and Table 8 stranded bare. Compact stranding (Table 5A), fixture wires, and sizes under 14 AWG are not included.
- Raceways: EMT (1/2-4), IMC, RMC (1/2-6), PVC-40 and PVC-80 (1/2-6), ENT (1/2-2), FMC (3/8-4), LFMC (3/8-4), LFNC-B (3/8-2). Not included: EMT 5 and 6 in. and IMC 5 and 6 in. (2023-labelled copies show them; not sourced twice), PVC types A and EB, LFNC-A and C, and other raceways. The count of identical conductors is shown up to 2000 only.
- Not checked: ampacity and the 310.15(C)(1) adjustment (see the ampacity app), voltage drop, bends and pulling, jam ratio, box fill, wireways. Table 1 applies to complete raceway systems (Note 2).