Grounding Conductor Size Calculator Equipment grounding conductor (EGC), NEC 250.122, and grounding electrode conductor (GEC), NEC 250.66
Size the equipment grounding conductor (EGC) for a circuit or feeder, or the grounding electrode conductor (GEC) for a service. Updates as you type. The calculation runs in your browser. A free account is needed after 3 calculations and to download results. Saving a project stores the inputs with your account.
Guide: Grounding Conductor Sizing
- Load the sample to see typical inputs, then replace every value with your project data.
- Check the units shown next to each input.
- Results and the drawing update as you type. Read the step-by-step table and any warnings.
Code basis and design decisions
- EGC: NEC 2023 Table 250.122 by the rating or setting of the overcurrent device ahead of the equipment, copper or aluminum/copper-clad aluminum.
- 250.122(B): where ungrounded conductors are increased in size from the minimum for ampacity (voltage drop, for example), the EGC is increased in proportion to the circular mil area (standard conductor areas), then rounded up to a standard size. Not required to be larger than the circuit conductors (250.122(A)).
- 250.122(F)(1)(b): parallel conductors in separate raceways get an EGC in each raceway, sized from the OCPD rating.
- GEC: NEC 2023 Table 250.66 by the largest ungrounded service-entrance conductor or the equivalent area of parallel sets. 250.66(A): sole connection to rod, pipe or plate electrodes need not be larger than 6 AWG Cu / 4 AWG Al; 250.66(B): to a concrete-encased electrode, 4 AWG Cu; 250.66(C): to a ground ring, the ring size.
Notes & limits
- Sizes only. EGC types, GEC installation and protection, and bonding jumpers are not checked here.
- Uses NEC 2023. Confirm the edition adopted by your jurisdiction.