OTWapps
OTWapps
All apps
HomeSearch
Civil / Site
Full Site and Stormwater DesignPeak Runoff (Rational Method)Stormwater Runoff (TR-55)Earthwork Cut & FillGutter Spread & Inlet CapacityOutlet Structure RatingRiprap Outlet ProtectionGrass-Lined Channel & SwaleADA Ramp SlopeStorm Pipe SizingCulvert Capacity & SizingDetention Pond RoutingOpen-Channel FlowPavement DesignVertical CurvesSanitary SewerParkingFire Service LineModified Rational DetentionLift StationFull Lift Station Design
Structural
Wind Main Frame (MWFRS)Wind Components & Cladding (C&C)Load CombinationsLive LoadsWood BeamWood ColumnJoist & Rafter SpanSteel BeamSteel ColumnSeismic Base ShearSpread FootingCantilever Retaining WallTruss AnalysisSign StructuresSnow LoadsWood Shear Wall & DiaphragmConcrete VolumeRebar Weight & QuantityConcrete BeamCrane Runway BeamHelical Piles and AnchorsSolar Roof AttachmentTilt-Up Wall PanelSolar Ground-Mount PileFence and Freestanding Wall Wind
Electrical
Voltage DropPower Factor CorrectionDwelling Service LoadLighting (Lumen Method)Conductor Ampacity & SizingTransformer Size & ProtectionAvailable Fault CurrentBox FillConduit FillMotor Branch CircuitGrounding Conductor SizingPhotometric Analysis & Lighting LayoutPV String SizingConductor Resistance and Impedance
Mechanical
Duct SizingExhaustVentilationPsychrometricsHydronic Pipe Pressure DropPump and Fan PowerNPSH Available
Plumbing
Water Supply SizingDrain Fixture UnitsStorm/Roof DrainGas Pipe SizingWater Heater SizingSump Pump SizingWater Hammer (Surge)Pipe Thermal Expansion and Loop
Fire Protection
Sprinkler K-FactorSprinkler Design Area & DemandHydrant Flow Test & Supply CurveFire Extinguisher PlacementOccupant Load
AboutPricingAccount

Transformer Size & Protection Calculator NEC 2023 450.3(B), 240.6(A), 240.21(C)

NEC 2023 Art. 450

Result

Result not calculated

Confirm the inputs and the method notes before using the result.

How this result was calculated

Inputs & units
Method & assumptions
References & limitations
Engineering aid only. Professional verification required. The method notes and tags on this page are the references this app cites.

By running a calculation you agree to the Terms of Use and Privacy Policy. Results are preliminary and must be verified by a licensed professional.

Your calculation

▤Result not calculatedComplete the inputs and review before calculating.

Downloads

Review inputs, calculation steps, and assumptions in one report.

US customary units; temperatures in °C as in the NEC tables.

How this calculation works

Code edition: NEC (NFPA 70) 2023: 450.3(B) and Table 450.3(B) (transformers 1000 V and less), its footnote 1 (next standard size) with 240.6(A) (2023 list, which includes 10 A), 240.21(C) and 240.4(F) as information, 240.4(D) and Table 310.16 with 110.14(C) for the optional secondary conductor. This is not the printed NFPA 70-2023: Table 450.3(B) and 240.21(C) were read in NFPA's own text; 240.4 and Table 240.6(A) come from agreeing secondary sources (see the notes).

  • Required inputs, no defaults: phase, primary voltage, secondary voltage, load basis and load, and the protection scheme. The transformer kVA is optional: left blank, the smallest standard size is chosen and the result says so. Conductors are sized only if you give both the material and the termination rating. Only the project name is otherwise optional. Unknown keys, true/false values and out-of-range values are rejected.
  • Voltages: line-to-line for 3-phase; the full winding voltage for 1-phase (240 V for a 120/240 V winding). Both must be 1000 V or less: over 1000 V (450.3(A)) is out of scope and rejected.
  • Standard kVA sizes are an app convention, not NEC: with the kVA left blank, the app picks the smallest of its common dry-type catalog ratings (makers differ). A kVA you enter is used as entered, with a warning if it is not a common rating.
  • Rated current is kVA x 1000 / V (1-phase) or kVA x 1000 / (sqrt(3) x V) (3-phase). sqrt(3) is irrational: it is computed with decimal at 28 significant digits. The current is shown rounded to 0.01 A (half up). That displayed value picks the row (9 A and 2 A thresholds; near a threshold it gives the lower percentage, never a looser result) and is used for the 125 % values. The 167 %, 250 % and 300 % round-down maxima and the secondary conductor minimum use the unrounded current, shown rounded down (maxima) or up (conductor) to 5 decimals, so the number shown never contradicts the rating or size. A required kVA computed from amps is rounded up to 0.001 kVA.
  • Table 450.3(B) uses the transformer rated current, not the load. Primary only: 125 % at 9 A or more, 167 % under 9 A, 300 % under 2 A. Primary and secondary: primary 250 %, secondary 125 % at 9 A or more and 167 % under 9 A.
  • Standard ratings: only the 125 % values may go to the next higher standard rating (footnote 1, 240.6(A)); the 167 %, 250 % and 300 % values are maximums and round down. The 2023 240.6(A) list starts at 10 A for breakers, so a maximum under 10 A gives "none" for a breaker (fuses also come in 1, 3, 6 and 601 A). Footnote 1 covers fuses and nonadjustable circuit breakers; an adjustable-trip breaker is a setting and has no input here, so the next-higher rule is applied to every breaker. Above 6000 A the list ends and there is no higher rating.
  • Secondary conductor (optional): 125 % of the rated secondary current, smallest Table 310.16 size in the termination column you enter, one conductor per phase, no ambient or adjustment correction. 240.4(D) is applied as in the ampacity app: for 14, 12 and 10 AWG copper and 12 and 10 AWG aluminum the device limit (15, 20, 30 A copper; 15, 25 A aluminum) must be at least the 125 % current, so a size whose limit is below it is skipped. The 125 % is the app's sizing basis; 240.4, 240.21(C), 215.2 and 210.19 govern the real conductors and the devices they feed.
  • 240.21(C) and 240.4(F) are information only: the primary device protects the secondary conductors only for a single-phase 2-wire or three-phase delta-delta 3-wire secondary; single-phase 3-wire and wye secondaries (for example 208Y/120 V) are not protected by the primary device. The summaries follow NFPA's 2023 text of 240.21(C)(1) to (C)(6); the lead-in sentence "Section 240.4(B) shall not be permitted for transformer secondary conductors" is quoted with them, while the 240.4(B) information step applies only to a conductor protected by a secondary device (you decide). The winding connection is not an input, so the app does not decide.
  • Not covered: over 1000 V (450.3(A)), motor control circuit transformers (430.72(C): excluded by the table's own lead-in), voltage transformers, autotransformers, grounding autotransformers, the footnote 3 thermal-overload alternative of the 250 % cells (primary device up to 6x or 4x rated current) and other Table 450.3(B) notes, short-circuit current, inrush and impedance, conduit fill and voltage drop, and the feeders and branch circuits the secondary supplies.