Code edition: NEC (NFPA 70) 2023, 2023 section numbering: Table 310.16, Table 310.15(B)(1)(1), Table 310.15(C)(1), 110.14(C), 240.4(D). Table values come from the NFPA fact sheet that reproduces the 2023 tables, cross-checked against secondary reproductions; they are to be confirmed against the printed NFPA 70-2023 by a licensed reviewer.
- Every input that changes the result is required and has no default (material, insulation rating, termination rating, ambient, number of current-carrying conductors, continuous and noncontinuous load). Only "check this size" is optional.
- Ambient is rounded up to the next whole degree C before the table lookup (conservative). Where the table shows no factor, the conductor is not permitted at that ambient.
- Rounding: the loads are shown rounded up and ampacities rounded down to 0.01 A, and pass/fail compares those displayed numbers, so a flag never contradicts the display.
- Two-part sizing test (210.19(A)(1) and 215.2(A)(1)): the conductor must pass both (a) noncontinuous + 125 % of continuous against the uncorrected Table 310.16 ampacity of the column of the lower of the insulation and termination ratings (110.14(C)), and (b) noncontinuous + 100 % of continuous against the insulation-column ampacity x ambient factor x adjustment factor. The 125 % is never multiplied by the correction factors. Each test is its own pass/fail and its own reason; the result says which test governs. "Usable ampacity" in the table is the lesser of the corrected ampacity and the termination-column ampacity, for information only.
- 240.4(D) small-conductor limits are a separate check against the 125 % design current (14 AWG Cu 15 A, 12 AWG Cu 20 A, 10 AWG Cu 30 A; 12 AWG Al 15 A, 10 AWG Al 25 A). The 240.4(B) next-size-up allowance is not used.
- Termination ratings: you state the equipment rating; a warning reminds you of the 110.14(C)(1) presumptions (60 C up to 100 A or 14 through 1 AWG unless marked or listed otherwise; 75 C above 100 A).
- Current-carrying conductor count is as you enter it (neutrals with harmonic current count; equipment grounds never count). Derating applies when conductors are bundled more than 24 in. without spacing; see the exceptions in 310.15(C)(1).
- Not covered in 0.1.0: parallel conductors, free-air cables (Table 310.17), direct burial detail, the 40 C table, rooftop sunlight, motor circuits (430.22), 100%-rated assemblies, 18 and 16 AWG. The size is for ampacity only (voltage drop is a separate app; conduit fill is not covered).