Full Site and Stormwater DesignPeak Runoff (Rational Method)Stormwater Runoff (TR-55)Earthwork Cut & FillGutter Spread & Inlet CapacityOutlet Structure RatingRiprap Outlet ProtectionGrass-Lined Channel & SwaleADA Ramp SlopeStorm Pipe SizingCulvert Capacity & SizingDetention Pond RoutingOpen-Channel FlowPavement DesignVertical CurvesSanitary SewerParkingFire Service LineModified Rational DetentionLift StationFull Lift Station Design
Structural
Wind Main Frame (MWFRS)Wind Components & Cladding (C&C)Load CombinationsLive LoadsWood BeamWood ColumnJoist & Rafter SpanSteel BeamSteel ColumnSeismic Base ShearSpread FootingCantilever Retaining WallTruss AnalysisSign StructuresSnow LoadsWood Shear Wall & DiaphragmConcrete VolumeRebar Weight & QuantityConcrete BeamCrane Runway BeamHelical Piles and AnchorsSolar Roof AttachmentTilt-Up Wall PanelSolar Ground-Mount PileFence and Freestanding Wall Wind
Electrical
Voltage DropPower Factor CorrectionDwelling Service LoadLighting (Lumen Method)Conductor Ampacity & SizingTransformer Size & ProtectionAvailable Fault CurrentBox FillConduit FillMotor Branch CircuitGrounding Conductor SizingPhotometric Analysis & Lighting LayoutPV String SizingConductor Resistance and Impedance
Mechanical
Duct SizingExhaustVentilationPsychrometricsHydronic Pipe Pressure DropPump and Fan PowerNPSH Available
Plumbing
Water Supply SizingDrain Fixture UnitsStorm/Roof DrainGas Pipe SizingWater Heater SizingSump Pump SizingWater Hammer (Surge)Pipe Thermal Expansion and Loop
Fire Protection
Sprinkler K-FactorSprinkler Design Area & DemandHydrant Flow Test & Supply CurveFire Extinguisher PlacementOccupant Load
AboutPricingAccount

Conductor Ampacity & Sizing Calculator NEC 2023 Table 310.16, 310.15, 110.14(C), 240.4(D)

NEC 2023 Table 310.16

Result

Result not calculated

Confirm the inputs and the method notes before using the result.

How this result was calculated

Inputs & units
Method & assumptions
References & limitations
Engineering aid only. Professional verification required. The method notes and tags on this page are the references this app cites.

By running a calculation you agree to the Terms of Use and Privacy Policy. Results are preliminary and must be verified by a licensed professional.

Your calculation

▤Result not calculatedComplete the inputs and review before calculating.

Downloads

Review inputs, calculation steps, and assumptions in one report.

US customary units; temperatures in °C as in the NEC tables.

How this calculation works

Code edition: NEC (NFPA 70) 2023, 2023 section numbering: Table 310.16, Table 310.15(B)(1)(1), Table 310.15(C)(1), 110.14(C), 240.4(D). Table values come from the NFPA fact sheet that reproduces the 2023 tables, cross-checked against secondary reproductions; they are to be confirmed against the printed NFPA 70-2023 by a licensed reviewer.

  • Every input that changes the result is required and has no default (material, insulation rating, termination rating, ambient, number of current-carrying conductors, continuous and noncontinuous load). Only "check this size" is optional.
  • Ambient is rounded up to the next whole degree C before the table lookup (conservative). Where the table shows no factor, the conductor is not permitted at that ambient.
  • Rounding: the loads are shown rounded up and ampacities rounded down to 0.01 A, and pass/fail compares those displayed numbers, so a flag never contradicts the display.
  • Two-part sizing test (210.19(A)(1) and 215.2(A)(1)): the conductor must pass both (a) noncontinuous + 125 % of continuous against the uncorrected Table 310.16 ampacity of the column of the lower of the insulation and termination ratings (110.14(C)), and (b) noncontinuous + 100 % of continuous against the insulation-column ampacity x ambient factor x adjustment factor. The 125 % is never multiplied by the correction factors. Each test is its own pass/fail and its own reason; the result says which test governs. "Usable ampacity" in the table is the lesser of the corrected ampacity and the termination-column ampacity, for information only.
  • 240.4(D) small-conductor limits are a separate check against the 125 % design current (14 AWG Cu 15 A, 12 AWG Cu 20 A, 10 AWG Cu 30 A; 12 AWG Al 15 A, 10 AWG Al 25 A). The 240.4(B) next-size-up allowance is not used.
  • Termination ratings: you state the equipment rating; a warning reminds you of the 110.14(C)(1) presumptions (60 C up to 100 A or 14 through 1 AWG unless marked or listed otherwise; 75 C above 100 A).
  • Current-carrying conductor count is as you enter it (neutrals with harmonic current count; equipment grounds never count). Derating applies when conductors are bundled more than 24 in. without spacing; see the exceptions in 310.15(C)(1).
  • Not covered in 0.1.0: parallel conductors, free-air cables (Table 310.17), direct burial detail, the 40 C table, rooftop sunlight, motor circuits (430.22), 100%-rated assemblies, 18 and 16 AWG. The size is for ampacity only (voltage drop is a separate app; conduit fill is not covered).

Related apps

  • Voltage Drop
  • Power Factor Correction
  • Dwelling Service Load
  • Transformer Size & Protection
  • Available Fault Current
  • All Electrical apps

Guides

  • How to calculate conduit fill under NEC 2023 Chapter 9
  • How to calculate voltage drop with NEC Chapter 9 tables
OTWapps
About Methods & references View plans Privacy Terms

Engineering aid only. Professional verification required.