OTWapps
OTWapps
All apps
HomeSearch
Civil / Site
Full Site and Stormwater DesignPeak Runoff (Rational Method)Stormwater Runoff (TR-55)Earthwork Cut & FillGutter Spread & Inlet CapacityOutlet Structure RatingRiprap Outlet ProtectionGrass-Lined Channel & SwaleADA Ramp SlopeStorm Pipe SizingCulvert Capacity & SizingDetention Pond RoutingOpen-Channel FlowPavement DesignVertical CurvesSanitary SewerParkingFire Service LineModified Rational DetentionLift StationFull Lift Station Design
Structural
Wind Main Frame (MWFRS)Wind Components & Cladding (C&C)Load CombinationsLive LoadsWood BeamWood ColumnJoist & Rafter SpanSteel BeamSteel ColumnSeismic Base ShearSpread FootingCantilever Retaining WallTruss AnalysisSign StructuresSnow LoadsWood Shear Wall & DiaphragmConcrete VolumeRebar Weight & QuantityConcrete BeamCrane Runway BeamHelical Piles and AnchorsSolar Roof AttachmentTilt-Up Wall PanelSolar Ground-Mount PileFence and Freestanding Wall Wind
Electrical
Voltage DropPower Factor CorrectionDwelling Service LoadLighting (Lumen Method)Conductor Ampacity & SizingTransformer Size & ProtectionAvailable Fault CurrentBox FillConduit FillMotor Branch CircuitGrounding Conductor SizingPhotometric Analysis & Lighting LayoutPV String SizingConductor Resistance and Impedance
Mechanical
Duct SizingExhaustVentilationPsychrometricsHydronic Pipe Pressure DropPump and Fan PowerNPSH Available
Plumbing
Water Supply SizingDrain Fixture UnitsStorm/Roof DrainGas Pipe SizingWater Heater SizingSump Pump SizingWater Hammer (Surge)Pipe Thermal Expansion and Loop
Fire Protection
Sprinkler K-FactorSprinkler Design Area & DemandHydrant Flow Test & Supply CurveFire Extinguisher PlacementOccupant Load
AboutPricingAccount

Box Fill Calculator (NEC 2023 314.16, Table 314.16(A), Table 314.16(B)(1))

Box (all required)
Counting rules (all required)
Conductors (one line per group: size, kind, count, loop length in., name; blank entries are fine; kinds: terminated, through, loop, pigtail, fixture_wire)
Advanced: full detailed inputs

Result

Result not calculated

Confirm the inputs and the method notes before using the result.

How this result was calculated

Inputs & units
Method & assumptions
References & limitations
Engineering aid only. Professional verification required. The method notes and tags on this page are the references this app cites.

By running a calculation you agree to the Terms of Use and Privacy Policy. Results are preliminary and must be verified by a licensed professional.

Your calculation

▤Result not calculatedComplete the inputs and review before calculating.

Downloads

Review inputs, calculation steps, and assumptions in one report.

Guide: OTW Box Fill (NEC 2023 314.16, Table 314.16(A), Table 314.16(B)(1))
  1. Load an example to see the expected inputs, then replace every example value with your project data.
  2. Work through the input sections in order. Confirm the displayed units, selected method and applicable code.
  3. Use Detailed calculation inputs for additional settings and nested rows. Add or remove rows without editing code.
  4. Run the calculation, then review the governing check, assumptions, warnings and detailed results. Verify the result before using it in a design.
Code edition and design decisions (NEC 2023)

Code edition: NEC (NFPA 70) 2023, 314.16(A) and Table 314.16(A) (standard metal boxes), 314.16(B)(1) to (B)(6) and Table 314.16(B)(1) (allowance per conductor; numbered Table 314.16(B) before 2023). This is not the printed NFPA 70-2023: rule text came from NFPA's 2023 committee statements and the 2024 IRC reproduction of NEC 2023 314.16(B), table values from several secondary reproductions (see the notes).

  • Grounding conductors follow the 2023 rule, not the older one: up to four equipment grounding conductors or bonding jumpers entering the box share one allowance at the largest size, and each additional one adds 1/4 allowance (314.16(B)(5)). An isolated-ground set is no longer a separate extra allowance (it was before 2020): isolated grounding conductors are just counted with the others. When more than four enter, the result shows what the older one-allowance rule would have given, for information only. Terminal block assemblies (B)(6) are new in 2023: one allowance each.
  • Required inputs, no defaults: box source, rings (blank = none), conductors, internal clamps yes/no, number of support-fitting types (0 is a real answer), devices (blank = none), number of grounding conductors (0 is a real answer) and terminal blocks (blank = none).
  • Largest conductor present (clamps, support fittings) is the largest size among everything you enter, including pigtails, fixture wires, grounding conductors and the conductors named for devices and terminal blocks. A device uses the largest conductor connected to its yoke, which you enter.
  • Loops: you enter the length of the unbroken loop or coil; 12 in. or more counts twice, less counts once. A pigtail or jumper that does not leave the box counts zero.
  • Fixture wires: 16 or 18 AWG fixture wires from a domed luminaire or similar canopy terminating in the box are omitted only when there are four or fewer in all; with more, all are counted. The separate grounding exception for a domed luminaire is not modeled: leave those conductors out of the grounding count yourself.
  • Support fittings: enter the number of different types (stud, hickey), one allowance per type.
  • Marked volumes (marked boxes, rings, extension rings, domed covers, assembled sections) are entered in cubic inches with at most 2 decimals, as marked; they are never silently rounded. Rings are added to every box in the smallest-box search; you choose compatible rings.
  • Multi-gang FS/FD and masonry boxes: enter the manufacturer's marked volume (box source "marked"). The table's multiple cover/gang volumes are not settled as per box or per gang, and the marking governs (314.16(A)(2)).
  • Exact arithmetic: allowances are multiples of 1/16 in3, so the required volume is exact (no rounding) and pass means required ≤ available.
  • Table 314.16(A): all 24 rows are included (round/octagonal, square, device, masonry, FS and FD). The maximum conductor counts are recomputed as floor(volume / allowance), not copied. For the FS and FD multiple cover/gang rows the sources do not settle whether the number is per gang or per box; it is used as the whole box volume, which errs on the safe side.
  • Not covered: conduit bodies 314.16(C), pull and junction boxes and conductors 4 AWG and larger (314.28), sizes smaller than 18 AWG, barriers (run once per space), box depth (314.24) and support. Locknuts, bushings and similar small fittings need no allowance.

Related apps

  • Voltage Drop
  • Power Factor Correction
  • Dwelling Service Load
  • Conductor Ampacity & Sizing
  • Transformer Size & Protection
  • All Electrical apps

Guides

  • How to calculate box fill under NEC 2023 314.16
  • How to calculate conduit fill under NEC 2023 Chapter 9
OTWapps
About Methods & references View plans Privacy Terms

Engineering aid only. Professional verification required.