How to calculate box fill under NEC 2023 314.16
NEC 314.16 box fill step by step: Table 314.16(B)(1) volume per conductor, counting rules for devices, clamps and grounds, Table 314.16(A) box volumes, and a worked example.
Run this in the free Box Fill appBox fill makes sure an outlet or junction box has enough volume for the conductors, devices and fittings inside it. NEC 314.16 converts everything in the box into a count of conductor volumes, then compares the total with the box's volume.
Step 1: Volume per conductor (Table 314.16(B)(1))
| Conductor size | Volume each (in.³) |
|---|---|
| 14 AWG | 2.00 |
| 12 AWG | 2.25 |
| 10 AWG | 2.50 |
| 8 AWG | 3.00 |
| 6 AWG | 5.00 |
Step 2: Count the allowances (314.16(B))
- Conductors: each conductor that originates outside the box and terminates or is spliced inside counts once. A conductor that passes through unbroken counts once. Conductors that never leave the box, such as pigtails, are not counted.
- Internal cable clamps: one allowance for all of them, based on the largest conductor in the box.
- Support fittings (fixture studs, hickeys): one allowance each.
- Devices: two allowances for each yoke or strap, based on the largest conductor connected to the device.
- Equipment grounding conductors: one allowance for all of them, based on the largest one. (Isolated grounding conductors add one more.)
Step 3: Box volume
Use Table 314.16(A) for standard metal boxes (for example, 3 in. × 2 in. × 3-1/2 in. device box: 12.5 in.³; 4 in. square × 1-1/2 in.: 21.0 in.³). Nonmetallic boxes and boxes not in the table use the volume marked by the manufacturer. Plaster rings, extension rings and domed covers add their marked volume.
Worked example: one receptacle, two 12/2 cables
- Four insulated 12 AWG conductors (two cables, two each): 4
- Equipment grounding conductors (all together): 1
- Internal cable clamps: 1
- Receptacle on one yoke: 2
- Total: 8 allowances × 2.25 in.³ = 18.0 in.³
A 3 × 2 × 3-1/2 in. device box (12.5 in.³) is too small. A 4 in. square × 1-1/2 in. box (21.0 in.³) works, plus whatever volume its device ring adds.
Common mistakes
- Counting every ground wire separately; they count as one allowance together.
- Counting clamps when the box has none, or forgetting them when it does.
- Using the device's conductor size instead of the largest conductor connected to it.
Run it in the app
The free Box Fill app does this calculation in your browser, shows each intermediate value and cites the code section on each line. You can try 3 calculations without an account. A free account is needed after that, and to download results.
Frequently asked questions
Do ground wires count in box fill?
Yes, but all equipment grounding conductors together count as a single allowance based on the largest one. An isolated equipment grounding conductor adds one more allowance.
How many allowances does a switch or receptacle take?
Two, for each yoke or strap, based on the largest conductor connected to that device.
Do pigtails count?
No. A conductor that originates and ends entirely inside the box, such as a pigtail, is not counted.
References
NFPA 70, National Electrical Code, 2023 edition: 314.16, Table 314.16(A) and Table 314.16(B)(1). Values above are quoted for illustration; check them against the edition adopted in your jurisdiction.
Related apps
More guides
- How to calculate conduit fill under NEC 2023 Chapter 9
- How to calculate voltage drop with NEC Chapter 9 tables
- ASCE 7-22 velocity pressure and components and cladding pressure: a worked example
- Rational Method peak runoff (Q = CiA) with a worked example
- Sprinkler K-factor: Q = K√P, with the 7 psi minimum
Published 2026-11-12.