Sprinkler K-factor: Q = K√P, with the 7 psi minimum

How sprinkler K-factor relates flow and pressure (Q = K x sqrt P), solving for any of the three, and why the NFPA 13 7 psi minimum often governs the end sprinkler.

Run this in the free Sprinkler K-Factor app

A sprinkler's K-factor describes how much water it discharges at a given pressure. It is the first number you need in a hydraulic calculation, because it ties the required flow at each sprinkler to the pressure the system must deliver.

The formula

Q = K √P

Rearranged: P = (Q / K)² and K = Q / √P.

Example 1: flow at a known pressure

K = 5.6 at P = 7 psi: Q = 5.6 × √7 = 14.8 gpm

Example 2: the end sprinkler in a density/area design

So the minimum pressure, not the density, governs this sprinkler. Larger coverage areas or higher densities move the result back to the density side.

After the end sprinkler

Work back toward the source: add pipe friction (Hazen-Williams) and elevation to find the pressure at the next sprinkler, compute its flow with the same formula, and repeat. Add the hose stream allowance from NFPA 13 (for light hazard, 100 gpm with a 30-minute duration) and compare the total demand with the water supply curve from a hydrant flow test.

Common mistakes

Run it in the app

The free Sprinkler K-Factor app does this calculation in your browser, shows each intermediate value and cites the code section on each line. You can try 3 calculations without an account. A free account is needed after that, and to download results.

Frequently asked questions

What is a K-factor of 5.6?

It means the sprinkler discharges 5.6 gpm at 1 psi, and flow increases with the square root of pressure. At 7 psi it discharges about 14.8 gpm.

What is the minimum pressure at a sprinkler?

NFPA 13 sets a minimum operating pressure of 7 psi for sprinklers. Some sprinklers have higher minimums in their listings.

How do I find pressure from flow?

Rearrange the formula: P = (Q / K) squared. For 25 gpm through a K 5.6 sprinkler, P = (25 / 5.6) squared = 19.9 psi.

References

NFPA 13, Standard for the Installation of Sprinkler Systems (minimum operating pressure, density/area method, hose stream allowance tables); sprinkler manufacturer data sheets. Values above are quoted for illustration; check them against the edition adopted in your jurisdiction.