How to calculate voltage drop with NEC Chapter 9 tables

Voltage drop for single-phase and three-phase circuits using NEC Chapter 9 Table 8 resistance and Table 9 impedance, the 3%/5% recommendation, and a worked 20 A example.

Run this in the free Voltage Drop app

Voltage drop is the voltage lost along the conductors between the source and the load. Too much drop makes motors run hot, lights dim and electronics misbehave. The NEC mostly treats it as a design recommendation rather than a rule, but the math is straightforward with the resistance and impedance tables in Chapter 9.

What the NEC says

The formulas

Using DC resistance R from Chapter 9 Table 8 (ohms per 1,000 ft), with one-way length L in feet and current I in amperes:

For AC circuits with larger conductors, power factor and conduit material matter. Table 9 gives AC resistance and reactance and an effective impedance at 0.85 power factor; substitute that effective Z for R in the same formulas.

Worked example: 20 A at 120 V, 100 ft one way

Stranded uncoated copper, Table 8 resistance: 12 AWG 1.98, 10 AWG 1.24, 8 AWG 0.778 ohms per 1,000 ft.

SizeVD = 2 × 100 × 20 × R / 1,000Percent of 120 V
12 AWG7.92 V6.6%
10 AWG4.96 V4.1%
8 AWG3.11 V2.6%

The 12 AWG conductor has the ampacity for a 20 A circuit but drops 6.6%. Meeting a 3% branch-circuit target at this length takes 8 AWG. Upsizing ungrounded conductors for voltage drop also requires a proportional increase in the equipment grounding conductor (250.122(B)).

Tips

Run it in the app

The free Voltage Drop app does this calculation in your browser, shows each intermediate value and cites the code section on each line. You can try 3 calculations without an account. A free account is needed after that, and to download results.

Frequently asked questions

Is voltage drop required by the NEC?

For general branch circuits and feeders, the 3% and 5% figures are in informational notes, which are recommendations. Specific articles such as 647.4(D) and 695.7 set mandatory limits.

Should I use Table 8 or Table 9?

Table 8 DC resistance is fine for small conductors and DC circuits. For AC circuits with larger conductors, Table 9 includes reactance and conduit type and gives a more accurate result.

Does upsizing for voltage drop change the ground wire?

Yes. When ungrounded conductors are increased in size, 250.122(B) requires the equipment grounding conductor to be increased proportionally by circular mil area.

References

NFPA 70, National Electrical Code, 2023 edition: Chapter 9 Tables 8 and 9; informational notes to 210.19 and 215.2; 647.4(D); 695.7. Values above are quoted for illustration; check them against the edition adopted in your jurisdiction.