ASCE 7-22 Components and Cladding Pressure Example
Compute ASCE 7-22 velocity pressure qz = 0.00256 Kz Kzt Ke V^2, then a low-rise components and cladding pressure with Kd and GCpi. What changed from ASCE 7-16.
Run this in the free Wind Components & Cladding (C&C) appEvery ASCE 7 wind calculation starts with the velocity pressure q. For components and cladding (C&C) on low-rise buildings you then multiply by the external and internal pressure coefficients. This guide walks through both with one set of example inputs.
Step 1: Velocity pressure (Eq. 26.10-1)
qz = 0.00256 Kz Kzt Ke V² (psf, V in mph)
- V: basic wind speed for the risk category, from the ASCE 7-22 maps or the ASCE Hazard Tool.
- Kz: velocity pressure exposure coefficient, Table 26.10-1, by exposure category and height.
- Kzt: topographic factor (1.0 on flat sites; Section 26.8 for hills and escarpments).
- Ke: ground elevation factor, Table 26.9-1 (1.0 is always permitted).
Change from ASCE 7-16: the directionality factor Kd is no longer in the velocity pressure equation. In ASCE 7-22 it is applied in the design pressure equations instead. Results come out the same if you apply it once, but mixing the 7-16 and 7-22 equations can apply it twice or not at all.
Step 2: Example inputs
- V = 150 mph (example value; read yours from the hazard tool for your site and risk category)
- Exposure C, mean roof height h = 30 ft, so Kh = 0.98 (Table 26.10-1)
- Kzt = 1.0, Ke = 1.0
qh = 0.00256 × 0.98 × 1.0 × 1.0 × 150² = 56.4 psf
Step 3: C&C pressure for a low-rise building (Eq. 30.3-1)
p = qh Kd [(GCp) − (GCpi)]
- Kd = 0.85 for buildings (Table 26.6-1).
- GCpi = ±0.18 for an enclosed building (Table 26.13-1). Check both signs.
- GCp comes from the Chapter 30 figures for the roof or wall zone and the effective wind area of the component. We use GCp = −1.0 here only to show the arithmetic; read the real value from the figure for your zone and area.
| Case | (GCp) − (GCpi) | p (psf) |
|---|---|---|
| GCpi = +0.18 | −1.0 − 0.18 = −1.18 | 56.4 × 0.85 × −1.18 = −56.6 |
| GCpi = −0.18 | −1.0 + 0.18 = −0.82 | −39.3 |
The governing suction is −56.6 psf (strength level). ASD load combinations use 0.6W, so the ASD value is about −34.0 psf. Chapter 30 also sets a minimum design pressure of 16 psf acting in either direction (Section 30.2.2).
Common mistakes
- Using the 7-16 velocity pressure equation (with Kd) and then applying Kd again.
- Using the tributary area instead of the effective wind area for GCp.
- Checking only one sign of internal pressure.
Run it in the app
The free Wind Components & Cladding (C&C) app does this calculation in your browser, shows each intermediate value and cites the code section on each line. You can try 3 calculations without an account. A free account is needed after that, and to download results.
Frequently asked questions
Where did Kd go in ASCE 7-22?
ASCE 7-22 removed the directionality factor Kd from the velocity pressure equation (Eq. 26.10-1) and placed it in the design wind pressure equations, such as Eq. 30.3-1 for low-rise components and cladding.
What GCpi should I use for an enclosed building?
Table 26.13-1 gives plus and minus 0.18 for enclosed buildings. Evaluate both signs and use the worse result for each zone.
Is the ASCE 7 wind pressure strength level or ASD?
ASCE 7 wind loads are strength-level. ASD load combinations multiply W by 0.6.
References
ASCE/SEI 7-22, Minimum Design Loads and Associated Criteria for Buildings and Other Structures: Chapter 26 (Eq. 26.10-1, Tables 26.6-1, 26.9-1, 26.10-1, 26.13-1) and Chapter 30 (Eq. 30.3-1). Values above are quoted for illustration; check them against the edition adopted in your jurisdiction.
Related apps
More guides
- How to calculate conduit fill under NEC 2023 Chapter 9
- How to calculate voltage drop with NEC Chapter 9 tables
- Rational Method peak runoff (Q = CiA) with a worked example
- Sprinkler K-factor: Q = K√P, with the 7 psi minimum
- How to calculate box fill under NEC 2023 314.16
Published 2026-11-12.